PITE 3561

Power Quality Analyzer

PITE3561 Power Quality Analyzer is Smart measurement and analysis for 3-phase/4-wire system, Compatible with EN50160 and testing frequency up to 1000Hz

 Why PITE?

An Easy-to-use power quality tools is a ”must-have” for any person who maintains or troubleshoots three phase power. PITE three-phase power quality meters help you locate, predict, prevent and troubleshoot problems in power distribution systems. We offer a full range of trouble-shooters for the prevention and analyzing of the power quality problem. It is not only your problem solver, but also money saver.

DOWNLOAD

Optional Current Clamps:

Features

Portable design and colorful touch screen
Applied to standard of EN 50160
Could test 3-phase volt, null line volt, 3-phase current, null line current, etc.
Up to 50 times harmonic testing with frequency spectrum graph
Power testing: 3-phase apparent power, active power, reactive power, power factor, and 3-phase electric power.
3-phase unbalance testing with vivid chart
Record at least 40 times of surge current
Testing for wave motion, short-time flicker and long-time flicker
Record up to 40 times of sag and swell
Could have long-time record for basic (stable) power quality parameter. Recording time interval adjustable between 1 second and 30 minutes.
Digital oscilloscope, checking waveform for voltage and current signal
With PITE Data View software for convenient analyzing of testing result

Technical Parameter

LCD: 7” 320 x 240 TFT touch screen
Input Impedance: >2MΩ,20pF
Measurement Range: Vrms 10~1000V
Current: 5A, 10A, 100A, 1000A, 1500A and 3000A (with customized current clamps)
Frequency: 30Hz~1000Hz
Harmonic Measurement: 1~50th
Inrush Current: 2000A
Peak Voltage: 1000V
Internal Memory: 16MB
External Memory:4GB
Communication Port: USB
W.(main unit): 1.2 kg
Battery: 14.4V 2000mAh Durable for 5 hours after full charge

Accuracy, resolution and range

 

Measurement range

Resolution

Accuracy

Volt/Amps/Hertz

Vrms (ac+dc)    

1 Vrms to 10 Vrms

10 Vrms to 100 Vrms

100 Vrms to 700 Vrms

0.001 Vrms

0.01 Vrms

0.1 Vrms

± 0.2 % of nominal voltage

Vpk

1 Vpk to 700 Vpk

0.001 Vrms

0.01 Vrms

0.1 Vrms

5 % of nominal voltage

Voltage Crest Factor (CF)

1.0 to > 10

0.01

± 5 %

Arms (ac+dc)

0 Arms to 10Arms

10 Arms to 100Arms

1000 Arms to 1000Arms

1000 Arms to 3000Arms

0.001 Arms

0.01 Arms

0.1 Arms

1 Arms

± 0.5 % ± 5 counts3

Apk

1Apk to 3000 Apk

1 A

± 5 %

A Crest Factor (CF)

1 to 10

0.01

± 5 %

Hz

30 Hz to70 Hz

0.01 Hz

± 0.01 Hz

Dips and swells

Vrms½ (ac+dc)  

0.0 % to 200 % of nominal voltage

0.1 Vrms

± 1 % of nominal voltage

Arms½ (ac+dc)

0 Arms to 10Arms

10 Arms to 100Arms

1000 Arms to 1000Arms

1000 Arms to 3000Arms

0.001 Arms

0.01 Arms

0.1 Arms

1 Arms

± 1 % ± 10 counts3

Threshold levels

Programmable thresholds in percent of nominal voltage

Event detection based upon ½ cycle rms voltages

Captures dips, swells, interruptions and rapid voltage changes

Duration

hhh,mm,ss,mmm

Half cycle

One cycle

 

Accuracy, resolution and range cont.

 

Measurement range

Resolution

Accuracy

Harmonics

 

Harmonic order (n)

DC, 1 to 50 grouping: harmonic groups according to IEC 61000-4-7

Inter-Harmonic order

Off, 1 to 49 grouping: harmonic and interharmonic subgroups according to IEC 61000-4-7

Vrms        Relative (%f):

 

Absolute:

 

0.0 % to 100.0 %

 

0.0 Vrms to 700 Vrms

 

 

0.1 %

 

0.1 Vrms

 

 

± 0.1 % ± n x 0.1 % (± 0.4 % for %r)

± 0.05 % of nominal voltage if

< 1 % of nominal voltage

± 5 % if ≥ 1 % of nominal voltage

Arms        Relative (%f):

               

                Absolute:

0.0 % to 100.0 %

0 Arms to 10Arms

10 Arms to 100Arms

1000 Arms to 1000Arms

1000 Arms to 3000Arms

0.1 %

0.001 Arms

0.01 Arms

0.1 Arms

1 Arms

± 0.1 % ± n x 0.1 % (± 0.4 % for %r)

± 5 % ± 5 counts

THD(n=40) (relative %f or %r)

0.0 % to 100.0 %

0.1 %

± 2.5 % V and A (± 5 % Watt)

Hz

0 Hz to 3000 Hz

1 Hz

± 1 Hz

Power and energy

Watt (VA, VAR)  

1.0 MW to 20.00 MW

 

0.1 kW to 1 kW1

± 0.5 % ± 10 counts3

kWh6 (kVA6, kVAR6)

00.00 kWhr to 200.0 GWhr1

0.01 Xhr to 100 Whr

± 0.5 % ± 10 counts3

Power Factor

0 to 1

0.001

± 0.005

Cos φ/DPF

0 to 1

0.001

± 0.005

Flicker

Pst (1min), Pst, Plt, PF5 instantenous

Flicker

0.00 to 20.00

0.01

Within ± 5 % of tabulated values according IEC61000-4-15

Unbalance

Volts (neg. and zero seq.)

0.0 % to 5.0 %

0.1 %

± 0.15 %

Current (neg. and zero seq.)

0.0 % to 20 %

0.1 %

± 1 %

Phase angle         volts

                   current

-360.0 ° to 0.0 °

-360.0 ° to 0.0 °

0.1 º

0.1 º

± 2 counts

± 5 counts3

Transient capture

Inrush mode

Arms (ac+dc)

0.0kArms to 3k Arms

0.001 Arms to 10 Arms

± 1 % of meas ± 5 counts

Inrush Duration

mm:ss:mmm between 7.5 s to 30 minutes selectable

10 ms

± 20 ms (Fnominal = 50 Hz)

           

 

Trend recording

Method

AutoTrend automatically records min, max and average values over time for all readings being displayed for the 3 phases and neutral simultaneously

Volts/Amps/Hertz, Harmonics, Power and Energy, Flicker, Unbalance and Mains Signaling4 mode

Sampling

5 readings/sec continuous sampling per channel

Recording time

From 30 min with 1 second display resolution up to 450 days with 6 hour display resolution.

Memory

16MB internal + 4GB external

Dips and Swells mode

Sampling

100/120 readings/sec continuous sampling per channel

Recording time

From 90 sec with 25 msec display resolution up to 450 days with 3 hr display resolution

Memory

16MB internal + 4GB external

Inrush currents and flicker PF5 mode

Sampling

100/120 readings/sec continuous sampling per channel

Recording time

From 7.5 sec with 25 msec display resolution up to 30 min with 500 msec display resolution for Inrush measurements and up to 2 hr with 2.5 sec display resolution for PF5 recordings

Memory

16MB internal + 4GB external

Logger mode

Sampling

Combination of 5 readings/sec and 100/1202 readings/sec continuous sampling per channel depending on the parameter measured

Recording time

Depends on selected readings and averaging time

Memory

16MB internal + 4GB external

Monitor mode

Sampling

Combination of 5 readings/sec and 100/120 readings/sec continuous sampling per channel depending on the parameter measured

Recording time

Up to 1 week with 10 min resoluto

Memory

16MB internal + 4GB external

Limits

According EN50160 or customer definable

 

Measurement method

Vrms, Arms

10/12 cycle contiguous non overlapping intervals using 500/416 samples per cycle in accordance with IEC 61000-4-30

Vpeak, Apeak

Absolute highest sample value within 10/12 cycle interval with 40 μs sample resolution

V Crest Factor

Measures ratio between the Vpeak and Vrms

A Crest Factor

Measures ratio between the Apeak and Arms

Hz

Measured every 10 sec in accordance with IEC61000-4-30

Vrms½, Arms½

Value is measured over 1 cycle, commencing at a fundamental zero crossing, and refreshed each half-cycle.

This technique is independent for each channel in accordance with IEC 61000-4-30.

Harmonics

Calculated from 10/12-cycle gapless harmonic group measurements on Voltage and Amps according to IEC 61000-4-7

Watt

Selectable Total or Fundamental real power display

Calculates average value of instantaneous power over 10/12 cycle period for each phase

Total Active Power PT = P1 + P2 + P3

 

 